Productinformation:
The Blue Line controller task is to control a floor central heating system.
Article no. | Type | Zones | Voltage | Pumps / boiler output | Heating / cooling | EAN |
9408 9110 605 | Standard | 6 | 230 V / 24 V | No / No | Yes / No | 42604 7795 0406 |
9408 9110 606 | Standard | 10 | 230 V / 24 V | No / No | Yes / No | 42604 7795 0413 |
9408 9110 608 | Standard plus | 6 | 230 V | Yes / No | Yes / Yes | 42604 7795 0420 |
9408 9118 608 | Standard plus | 6 | 24 V | Yes / No | Yes / Yes | 42604 7795 1854 |
9408 9110 609 | Standard plus | 10 | 230 V | Yes / No | Yes / Yes | 42604 7795 0581 |
9408 9118 609 | Standard plus | 10 | 24 V | Yes / No | Yes / Yes | 42604 7795 1861 |
9408 9110 610 | Comfort | 6 | 230 V | Yes / Yes | Yes / Yes | 42604 7795 1090 |
9408 9118 610 | Comfort | 6 | 24 V | Yes / Yes | Yes / Yes | 42604 7795 1878 |
9408 9110 611 | Comfort | 10 | 230 V | Yes / Yes | Yes / Yes | 42604 7795 1106 |
9408 9118 611 | Comfort | 10 | 24 V | Yes / Yes | Yes / Yes | 42604 7795 1885 |
Name | Description |
Operating voltage: | 230V AC |
Actuator: | 6 heating zones: max. 15 10 heating zones: max. 18 |
Rated load of all drives: | max. 24 W |
Pump / boiler control - Activation delay: - Stopping time fixed / adjustable: |
2 min 2 min |
Pump protection function: | 14 days for 1 minute |
Standard | Standard plus | Comfort | ||||||||
Operating voltage | 230 V / 24 V | 230 V | 24 V | 230 V | 24 V | 230 V | 24 V | 230 V | 24 V | |
Zones | 6 | 10 | 6 | 10 | 6 | 10 | ||||
Type | Wired | |||||||||
Protective conductor Intermediate connector |
x | x | x | x | ||||||
Networked by terminal for Pump / boiler circuit |
x | x | x | x | ||||||
Networked by terminal for dew point sensor |
x | x | x | x | ||||||
Expanded pump / boiler control Stopping time configurable |
x | x | x | x | ||||||
Simple Pump control |
x | x | x | x | ||||||
Signal input for temperature limiter or dew point sensor |
x | x | x | x | x | x | x | x | ||
Reduction duct - Connection for an external system clock |
x | x | x | x | x | x | x | x | x | x |
Changeover connection signal for heating / cooling |
x | x | x | x | x | x | x | x | ||
Timer module - housing - cover with integrated system clock |
Optional | |||||||||
Control direction normally closed (NC) / normally open (NO) |
NC/NO | NC (without pump controller as NO) | Selectable | |||||||
Function signaling by LEDs |
x | |||||||||
Power supply | 24 V: System transformer with Euro connection / external voltage source 230 V: Euro plug / external voltage source |
|||||||||
Max. power consumption (without pump / boiler device) |
24 V : max. 36 VA 230 V : max. 50 VA |
|||||||||
Max. number of thermostats |
6 | 10 | 6 | 10 | 6 | 10 | ||||
Max. number of connection terminals for actuators |
15 | 21 | 15 | 21 | 15 | 21 | ||||
Max. rated load of all drives |
24 V : 24 W 230 V : -- |
|||||||||
Temperature limiter or dew point sensor |
Potential-free normally closed, switchable, 24 V / 230 V, 8 A | |||||||||
Weight | 410 g | 424 g | 428 g | 448 g | 442 g | 466 g | ||||
Dimensions (W x H x D) | 90 x 326 x 52 mm |